PMS CHECK-IN
Guests check-in at the front desk
The room is declared rented
The thermostat in the room resets to to an initial CHeCK-IN temperature
rented/UNoccupied mode
rented/occupied mode
CHECK-OUT
UNrented/occupied mode
UNrented/UNoccupied mode
Room is declared UNrented / occupied
Door signals to thermostat that staff exists room and motion is NOT detected within 2 minutes
Temperature setpoint tolerance increased to UNRENTED/UNOCCUPIED mode for cost saving
Door lock signals to thermostat as staff enters room and motion is detected within 2 minutes
If no previous staff member adjusted the target temperature after the checkout, the temperature is maintained within the unrented band
Guests checks out at the front desk
The room is declared UNRented / UNoccupied
Thermostat display is set to off and setpoint tolerance range is increased to UNRENTED/UNOCCUPIED mode for energy savings
Room is declared rented / UNoccupied
Door lock signals to the thermostat as guest enters, and motion is detected within 10 minutes
Room is declared rented / occupied
Temperature is maintained around the target rented / occupied temperature band
Temperature setpoint tolerance is increased to reduce system cycling during rented / UNoccupied mode
Door lock signals to the thermostat as guest exists, and motion is not detected within 10 minutes